How to Troubleshoot Bus Cable Failures (EMI, Bending, Termination Issues)

By Eileen Harvey 

In industrial automation systems, the effectiveness of bus communication protocols such as PROFIBUS, CAN-Bus and Ethernet/IP is fundamentally tied to the integrity of the physical cabling used in these networks. Even minor issues within the cabling can trigger significant communication failures, leading to system downtime that can have cascading effects on production processes and ultimately result in costly repairs.  

Common problems associated with bus cables include electromagnetic interference (EMI), which can disrupt data transmission; physical damage caused by bending, crushing or mishandling the cables; and improper termination of connections that can lead to signal reflections and loss of data. Addressing these issues promptly is crucial, as any delay in diagnosis or repair can exacerbate the problem and lead to greater operational disruptions. 

Common Causes of Bus Cable Failures 

Before beginning troubleshooting, it is important to understand the most common reasons bus cables fail. EMI is one cause, with external sources such as motors, transformers or radio signals disrupting communication. Physical damage is another, as bending, crushing or mishandling can harm the insulation or conductors. Incorrect termination also leads to issues, since missing or improperly installed termination resistors cause reflections that interfere with data flow. Poor grounding can introduce electrical noise into the system, while connector or pin problems such as corrosion or looseness impair signal transmission. Finally, cable quality plays a significant role, as substandard or incompatible cables often lead to reliability problems. 

Step-by-Step Troubleshooting Guide 

Visual Inspection 

Start with a detailed visual inspection of the system. Look for physical signs of damage such as cuts, abrasions or exposed conductors. Check for sharp bends or kinks that may have caused internal conductor damage. Inspect connectors to ensure that pins are intact, free of corrosion and properly seated. Confirm that the cable is routed away from strong EMI sources such as motors or fluorescent lighting, and verify that cables are properly supported to prevent undue stress. 

Check for Proper Termination 

Next, confirm that termination resistors are correctly installed at both ends of the network. For example, CAN-Bus typically requires 120-ohm termination. A multimeter can be used to measure resistance across the cable ends. A reading close to the expected value indicates proper termination, while readings that are unusually low or high suggest missing or faulty resistors. 

Test for EMI Interference 

To detect electromagnetic interference, use a field strength meter or an oscilloscope to check the signal lines. If possible, temporarily disconnect or relocate potential sources of EMI such as motors, transformers, radio transmitters or fluorescent lights. Monitor the system to see if performance improves when these sources are removed or shielded. 

Measure Signal Integrity 

An oscilloscope can also be used to check the quality of the waveform. Look for distortions, reflections or noise spikes that indicate signal problems. A cable tester or network analyzer can verify continuity and impedance matching. For longer cable runs, check for attenuation, which may require using cables designed for low signal loss. 

Check for Bending or Mechanical Damage 

Verify that the cables are not bent beyond their minimum bend radius as specified by the manufacturer. Ensure that there is sufficient slack to prevent tight bends. Any cables showing internal damage or wear should be replaced. 

Test Connectors and Terminals 

Loose connectors should be tightened and corroded or damaged ones should be replaced. If corrosion is minor, contact cleaner can restore reliable performance. 

Replace Suspect Cables 

If damaged or questionable cables are found, replace them with known-good cables from inventory. Test the system afterward to confirm whether the issue has been resolved. 

Check Network Topology and Grounding 

Confirm that the network topology follows the proper standard, such as linear bus configurations or approved star arrangements. All devices should share a common ground. Ground testing tools can help identify ground loops or floating grounds that may cause instability. 

Additional Tips for Reliable Bus Communication 

Maintaining proper cable routing reduces EMI. Data cables should always be kept separate from power lines. Using high-quality industrial-grade cables from trusted suppliers, such as TKD Kabel’s PROFIBUS DP FMS FIP 1 Pair 150 Ohm 22 AWG, ensures long-term reliability. Regular maintenance is also important, including periodic inspections and testing, especially in harsh or demanding environments. Keeping detailed documentation of cable layouts, connector types and test results makes future troubleshooting more efficient. 

Recommendations for Preventing Future Failures 

Preventing failures begins with selecting cables designed for industrial environments that have the right shielding and insulation. Proper grounding and shielding techniques should always be implemented. Avoid excessive bending or mechanical stress, and use cable management systems to prevent accidental damage. Periodic testing with cable testers and network analyzers provides early detection of potential problems. 

Facts to Know 

Several technical facts highlight the importance of proper installation and maintenance. EMI interference can reduce signal quality by as much as 80 percent. Industrial cables generally require a minimum bend radius of 6 to 10 times the cable diameter. Proper termination can reduce reflections by up to 90 percent, greatly improving data integrity. Shielded twisted pair cables are standard in PROFIBUS and CAN-Bus systems because of their ability to combat EMI. Finally, routing cables away from power lines and strong EMI sources is an essential best practice. 

FAQs (Frequently Asked Questions) 

Q1: How do I identify if EMI is causing my communication issues?  
A: Use an oscilloscope or field strength meter to detect noise spikes or fluctuations. Moving or shielding cables away from EMI sources often improves communication. 

Q2: Can bending cables cause failures even if they look intact?  
A: Yes. Excessive bending can damage internal conductors or insulation, leading to intermittent failures. Always follow the manufacturer's bend radius guidelines. 

Q3: What is the best way to prevent termination issues?  
A: Ensure that termination resistors are correctly installed at both ends of the bus, and 